Shielded Wall logo

Standards and Testing

The international standards we reference in design, production and acceptance testing.

Test Yaklaşımımız

Ekranlı yapıların performansı ancak ölçümle kanıtlanır. Kurulumlarımızın ardından, proje şartnamesine göre IEEE 299 veya eşdeğer yöntemlerle saha kabul testleri gerçekleştirilebilir; ölçümler manyetik alan, elektrik alan ve düzlem dalga bileşenlerini kapsar.

Test hizmetleri, talebe göre bağımsız akredite laboratuvarlar eliyle de yürütülebilir. Sertifikasyon gerektiren TEMPEST projelerinde yetkili ulusal otoritelerin süreçlerine uygun altyapı hazırlığı yapılır.

Reference Standards

IEEE 299

IEEE Standard Method for Measuring the Effectiveness of Electromagnetic Shielding Enclosures

The internationally accepted core test method for measuring the shielding effectiveness of shielded rooms and enclosures. Covers magnetic field, electric field and plane wave measurements.

Application: Ekranlı oda kabul testleri

EN 50147-1

Anechoic Chambers – Shield Attenuation Measurement

European standard defining the measurement method for the shield attenuation of shielded structures. Referenced in EMC test chambers and laboratory infrastructure.

Application: EMC test odaları

MIL-STD-188-125

High-Altitude Electromagnetic Pulse (HEMP) Protection

US military standard for protecting critical military and fixed communication facilities against high-altitude electromagnetic pulse (HEMP/NEMP). Defines point-of-entry protection, shielding and filtering requirements.

Application: HEMP / NEMP koruma

MIL-STD-461

Requirements for the Control of Electromagnetic Interference Characteristics

US military standard defining EMI emission and susceptibility requirements for military equipment. Referenced in performance verification of power and signal line filters.

Application: EMI filtre ve ekipman testleri

MIL-STD-285

Attenuation Measurements for Enclosures (Legacy)

Historic US military standard for attenuation measurement of shielded enclosures. Largely superseded by IEEE 299 but still referenced in many specifications.

Application: Ekranlama zayıflatma ölçümü

NATO SDIP-27

NATO TEMPEST Requirements and Evaluation Procedures

NATO document defining TEMPEST equipment levels (Level A/B/C) and evaluation procedures. The core reference for emanation security of systems processing classified information.

Application: TEMPEST cihaz ve sistemler

NATO SDIP-28

NATO Zoning Procedures

NATO procedure defining the zoning of facilities (Zone 0-3) according to electromagnetic emanation risk. Used in layout planning of TEMPEST rooms and secure areas.

Application: Tesis bölgelendirme

NSA TEMPEST 1-92

NSTISSAM TEMPEST/1-92 – Compromising Emanations Laboratory Test Requirements

Defines laboratory test requirements for compromising emanations in US national security systems. Accepted as an international reference in TEMPEST product verification.

Application: TEMPEST laboratuvar testleri

Important Note

The standards listed on this page are the technical references used in our design, production and testing processes. Upon request, our products can be tested against the relevant standards in accredited laboratories. Certificates and test reports applicable to a specific project are documented separately under contract.